The DAB Evosta 2 is an electronic, low-energy consumption circulator pump designed for water circulation in various domestic heating and air conditioning systems. This manual provides essential information for the safe and efficient installation, operation, and maintenance of your Evosta 2 pump.

The Evosta 2 series combines the robustness of mechanical circulators with the advantages of electronic control. It features a synchronous permanent magnet motor, a frequency converter, and an efficiency index (EEI) of ≤ 0.18, ensuring high efficiency and reliability. Its compact design and comprehensive performance make it suitable for replacing older three-speed circulators.

DAB Evosta 2 Circulator Pump
Figure 1: DAB Evosta 2 Circulator Pump. This image shows the main unit with its green and black housing, control panel, and threaded connections.

2. Maklumat Keselamatan

Penting: Baca semua arahan keselamatan sebelum pemasangan atau pengendalian. Kegagalan mematuhi arahan ini boleh mengakibatkan renjatan elektrik, kebakaran atau kecederaan serius.

  • Pemasangan dan penyelenggaraan mesti dilakukan oleh kakitangan yang berkelayakan sahaja.
  • Ensure the power supply is disconnected before performing any work on the pump.
  • The pump operates with hot liquids; allow it to cool before handling to prevent burns.
  • Protect the pump from moisture and direct water spray.
  • Do not operate the pump if it is damaged or if the electrical cable is frayed.
  • The pump is designed for clean, non-viscous, chemically neutral liquids. Do not use with flammable or corrosive liquids.

3. Penerangan dan Ciri Produk

The Evosta 2 circulator pump is engineered for optimal performance and durability. Key features include:

  • Kecekapan Tenaga: Equipped with a synchronous permanent magnet motor and frequency converter, achieving an EEI ≤ 0.18.
  • Pembinaan Teguh: Cast iron pump body with cataphoresis treatment, wet rotor motor, and ceramic shaft mounted on ceramic bushings lubricated by the pumped liquid.
  • Perlindungan Bersepadu: Internal motor protection eliminates the need for external overload protection.
  • Kawalan Mesra Pengguna: A single sequential adjustment button on the control panel simplifies settings.
  • Akses Penyelenggaraan: Direct access to the crankshaft for potential unlocking.
  • High Protection Rating: Tahap perlindungan IPX5.
DAB Evosta 2 Features and Benefits
Gambar 2: Lebihview of Evosta 2 features, highlighting its energy efficiency (EEI ≤ 0.18) and 5-year warranty. The image also shows different models in the Evosta series.

Pam casing is made of steel, with a technopolymer impeller. The rotor sleeve, stator sleeve, and closing flange are stainless steel. The thrust ring is graphite, and the sealing rings are EPDM. An air bleed plug made of brass is integrated.

DAB Evosta 2 Exploded View and Materials List
Rajah 3: Meletup view of the Evosta 2 pump with a corresponding list of materials for each component, illustrating the internal construction.

4. Pemasangan

Proper installation is crucial for the pump's performance and longevity. Follow these guidelines:

  • Kedudukan Pemasangan: Install the pump with the motor axis horizontal.
  • Sambungan Paip: The Evosta 2 40-70/130 is equipped with 1" (G 1") threaded connections. The 1/2" designation refers to the thread intended for connection to 1" to 1/2" reduced female fittings. Verify compatibility with your existing pipes or fittings.
  • Bekalan Kuasa: Connect the pump to a single-phase 1 x 230 V ~ 50/60 Hz power supply. Ensure the electrical installation complies with local regulations.
  • Pembilasan Sistem: Before starting the pump, ensure the system is thoroughly flushed to remove any debris that could damage the pump.
  • Pembersihan Udara: The pump includes an integrated air bleed plug. After filling the system, open the plug to release any trapped air.

Refer to the dimensional drawings for precise measurements and connection details to ensure proper fitment within your system.

DAB Evosta 2 Dimensional Drawing
Figure 4: Dimensional drawing of the Evosta 2 40-70/130 pump, showing key measurements (in mm) and pump connection details (1" G thread).

5. Operasi

The Evosta 2 pump features a control panel on the electronic control device cover, allowing for easy adjustment of its functions. The pump offers nine setting options, selectable via the MODE button.

  • Pilihan Tetapan: Press the MODE button to cycle through the available settings. The selected setting is indicated by six illuminated segments on the display.
  • Mod Pengendalian: The pump supports various operating modes, typically including proportional pressure, constant pressure, and constant curve modes, to adapt to different system requirements.
DAB Evosta 2 Operating Modes and Settings
Figure 5: Diagram illustrating the different operating modes (Proportional Pressure, Constant Pressure, Constant Curve) and an example of model designation for the Evosta series.

Consult the specific icons or indicators on your pump's control panel to identify the active operating mode and adjust as needed for your heating or cooling system.

6. Penyelenggaraan

Regular maintenance ensures the long-term reliability and efficiency of your Evosta 2 pump.

  • Pembersihan Udara: Periodically check and, if necessary, open the integrated brass air bleed plug to release any air trapped in the pump. This prevents cavitation and ensures smooth operation.
  • Crankshaft Unlocking: In case of a blockage, the pump provides direct access to the crankshaft for manual unlocking. Refer to the technical diagrams for the exact location.
  • Pembersihan: Keep the exterior of the pump clean and free from dust and debris. Do not use abrasive cleaners.
  • System Fluid: Ensure the pumped liquid remains clean and free of solid substances and mineral oils. Glycol content should not exceed 30%.
  • No Overload Protection Needed: Due to internal motor protection, no external overload protection is required.

7. Penyelesaian masalah

If you encounter issues with your Evosta 2 pump, consider the following common problems and solutions:

  • Pam Tidak Bermula:
    • Periksa bekalan kuasa dan pemutus litar.
    • Ensure the pump is properly connected to the electrical mains.
    • Verify that the motor is not seized. Use the direct access to the crankshaft to attempt manual unlocking if necessary.
  • No Flow or Reduced Flow:
    • Check for air in the system. Bleed air using the integrated plug.
    • Inspect for blockages in the pipes or pump impeller.
    • Ensure valves in the system are open.
    • Verify the selected operating mode and setting are appropriate for the system's requirements.
  • Bunyi Luar Biasa:
    • Noise can indicate air in the system. Purge air.
    • Check for foreign objects in the pump.
    • Ensure the pump is securely mounted and not vibrating excessively.

If problems persist after attempting these solutions, contact qualified service personnel or DAB customer support.

8. Spesifikasi Teknikal

ParameterNilai
ModelEvosta 2 40-70/130
Nombor Bahagian Pengilang60231855
Julat Operasi0.4 – 3.6 m³/h with head up to 6.9 meters
Julat Suhu Cecair0 °C hingga +110 °C
Tekanan Operasi10 bar (1000 kPa)
Indeks PerlindunganIPX5
Kelas PenebatF
PemasanganMotor axis horizontal
Bekalan Kuasa1 x 230 V ~ 50/60 Hz
Pumped LiquidClean, free of solids/mineral oils, non-viscous, chemically neutral, water-like (max 30% glycol)
Bahan Badan PamBesi tuang dengan rawatan kataforesis
Motor Casing BahanKeluli
Bahan PendesakTechnopolymer
Bahan AciSeramik
Berat badan1.86 kg
Dimensi Pakej15 x 14 x 10 cm
DAB Evosta 2 Performance Curves and Data Table
Figure 6: Performance curves and detailed technical data table for various Evosta 2 models, including flow rate (Q) and head (H) values.

9. Waranti dan Sokongan

The DAB Evosta 2 circulator pump comes with a Waranti 5 tahun, ensuring peace of mind regarding its quality and durability. This warranty covers manufacturing defects under normal use conditions.

For technical assistance, warranty claims, or spare parts inquiries, please contact your authorized DAB dealer or customer support. When contacting support, please have your model number (60231855) and purchase date available.

Information regarding the availability of spare parts is not provided in the product data. Please consult your dealer for specific spare part availability.