Vertiv GXE3-1000IRT2UXL

Vertiv Liebert GXE3-1000IRT2UXL UPS User Manual

Model: GXE3-1000IRT2UXL

1. Pengenalan

The Vertiv Liebert GXE UPS is an in-line dual conversion single-phase inverter designed to provide robust power protection for critical IT equipment. This system ensures continuous and reliable power, safeguarding connected devices from various AC sector disruptions through its advanced inline double conversion technology. Its flexible design allows for both rack-mount and tower configurations, making it suitable for diverse application environments.

2. Maklumat Keselamatan

Sila baca dan fahami semua arahan keselamatan sebelum memasang, mengendalikan atau menyelenggara UPS. Kegagalan mematuhi arahan ini boleh mengakibatkan renjatan elektrik, kebakaran atau kecederaan serius.

3. Produk Lebihview

3.1 Ciri-ciri Utama

3.2 Panduan Visual

Depan view of the Vertiv Liebert GXE3-1000IRT2UXL UPS in tower configuration, showing the LCD display and control buttons.
Rajah 3.2.1: Depan View of the UPS. This image displays the front panel of the UPS, highlighting the LCD screen and user interface buttons for status monitoring and configuration.
belakang view of the Vertiv Liebert GXE3-1000IRT2UXL UPS, showing input power, circuit breaker, and eight IEC C13 output receptacles.
Rajah 3.2.2: Belakang View of the UPS. This image shows the back panel, detailing the power input, circuit breaker, and eight IEC C13 output ports for connecting protected devices.
Tiga suku view of the Vertiv Liebert GXE3-1000IRT2UXL UPS in tower configuration with base stands.
Figure 3.2.3: UPS in Tower Configuration. This perspective view illustrates the UPS standing upright with its included base stands, suitable for tower deployment.
sebelah view of the Vertiv Liebert GXE3-1000IRT2UXL UPS in tower configuration, showing the ventilation grilles.
Rajah 3.2.4: Sisi View of the UPS. This image provides a side profile, highlighting the ventilation grilles essential for proper heat dissipation.

4. Persediaan

4.1 Membongkar dan Pemeriksaan

Carefully unpack the UPS and its accessories. Inspect for any shipping damage. Retain the packaging for future use or return.

4.2 Penempatan

Place the UPS in a well-ventilated area, away from direct sunlight, heat sources, and excessive dust or moisture. Ensure sufficient clearance around the unit for proper airflow.

4.3 Configuration (Tower/Rack-Mount)

The GXE3-1000IRT2UXL can be deployed as a tower unit using the included stands or installed in a standard 19-inch rack using an optional rack-mount kit (sold separately). Follow the instructions provided with the rack-mount kit for rack installation.

4.4 Sambungan Elektrik

  1. Kuasa Input: Connect the UPS input power cord to a grounded electrical outlet. Ensure the outlet provides the correct voltage (230V) and current capacity.
  2. Peranti Output: Connect your critical IT equipment (servers, networking devices, etc.) to the IEC C13 output receptacles on the rear of the UPS. Do not overload the UPS beyond its rated capacity (900W).
  3. Pelabuhan Komunikasi: For monitoring and management, connect the appropriate communication cables (USB, RS-232, or optional network card) to your computer or network.

4.5 Kuasa Permulaan

After all connections are secure, press the power button on the front panel to turn on the UPS. The LCD display will illuminate, and the UPS will perform a self-test. Allow the batteries to charge for at least 4 hours before connecting critical loads for optimal runtime.

5. Mengendalikan UPS

5.1 Paparan dan Kawalan LCD

The user-friendly LCD display provides real-time status information, including input/output voltage, load level, battery capacity, and operational mode. Use the navigation buttons next to the LCD to scroll through menus and configure settings.

5.2 Mod Pengendalian

5.3 Pengurusan Perisian

For enhanced monitoring and management, install the Vertiv Power Assist software on a connected computer for local control and graceful shutdown. For network-wide management, utilize Vertiv Power Insight or an optional Vertiv Liebert Intellislot IS-UNITY Network Management Card.

6. Penyelenggaraan

6.1 Penggantian Bateri

The Vertiv Liebert GXE3-1000IRT2UXL features hot-swappable internal batteries, allowing for replacement without powering down connected equipment. Refer to the detailed battery replacement guide available on the Vertiv support website for specific instructions. Always use genuine Vertiv replacement batteries.

6.2 Pembersihan

Periodically clean the exterior of the UPS with a soft, dry cloth. Ensure ventilation openings are free from dust and debris to maintain proper airflow and prevent overheating.

6.3 Pemeriksaan Berkala

Regularly check the UPS status via the LCD display or management software. Verify that input and output connections are secure and that the UPS is operating in the desired mode.

7. Penyelesaian masalah

This section provides solutions to common issues you may encounter with your UPS. For more complex problems, contact Vertiv technical support.

MasalahKemungkinan PuncaPenyelesaian
UPS tidak dihidupkan.No input power; UPS circuit breaker tripped; Battery deeply discharged.Check power cord connection and wall outlet. Reset the circuit breaker. Allow UPS to charge for several hours.
UPS berbunyi bip berterusan.Overload condition; Low battery.Reduce connected load. Allow batteries to recharge.
UPS kerap bertukar kepada mod bateri.Kuasa utiliti tidak stabil; Tetapan sensitiviti terlalu tinggi.Check utility power quality. Adjust UPS input sensitivity via LCD or software.

8. Spesifikasi

AtributNilai
Nombor ModelGXE3-1000IRT2UXL
Kapasiti (VA/W)1000VA / 900W
Input Voltage230V
Faktor Kuasa Keluaran0.9
Faktor Bentuk2U Tower / Rack-Mount Convertible
Peti Hasil8 x IEC60320 C13
TeknologiDual Conversion Online
Efficiency (Online Mode)Sehingga 91%
Efficiency (ECO Mode)Sehingga 96%
Masa Isi Ulang< 4 hours to 90% (internal batteries)
Dimensi (Pakej)17.24 x 16.93 x 3.39 inci
Berat Barang35.2 paun
ASINB0DX6YTYFZ
UPC767041034967, 767041034394

9. Waranti dan Sokongan

The Vertiv Liebert GXE3-1000IRT2UXL UPS comes with a standard manufacturer's warranty. Please refer to the warranty card included with your product or visit the official Vertiv webtapak untuk terma dan syarat jaminan terperinci.

Sokongan Teknikal

For technical assistance, troubleshooting, or service inquiries, please contact Vertiv customer support. Contact information and support resources can be found on the official Vertiv webtapak: www.vertiv.com/en-us/support/

Dokumen Berkaitan - GXE3-1000IRT2UXL

Praview Vertiv Liebert GXE UPS 1-3kVA Installer/User Guide - Installation and Operation
Comprehensive installer and user guide for the Vertiv Liebert GXE UPS 1-3kVA series, covering installation, operation, maintenance, troubleshooting, and specifications for reliable power protection.
Praview Vertiv Liebert GXE UPS: High Performance Power Protection
Explore the Vertiv Liebert GXE, an essential and affordable online double-conversion UPS system offering robust power protection for 6000 VA to 10000 VA applications. Features include high efficiency, flexible rack/tower mounting, scalable runtime, and advanced management.
Praview Vertiv Liebert GXT5 UPS: Perlindungan Kuasa Pintar & Cekap | Produk Lebih Lanjutview
Terokai siri UPS Vertiv Liebert GXT5, yang menawarkan perlindungan kuasa pintar dan cekap untuk aplikasi misi kritikal. Ini lebihview memperincikan ciri-ciri, spesifikasi, keluargaview, pakej perkhidmatan, aksesori dan pilihan pemasangan, menonjolkan reka bentuk padat, kecekapan tinggi dan keupayaan pengurusan lanjutan.
Praview Vertiv Liebert HPM: Penyelesaian Penyejukan Pusat Data Berprestasi Tinggi (4-30 kW)
Terokai siri Vertiv Liebert HPM, menawarkan penyelesaian penyaman udara yang cekap dan boleh dipercayai untuk pusat data dan persekitaran kritikal. Temui spesifikasi teknikal, ciri utama dan aplikasi untuk kapasiti penyejukan dari 4 hingga 30 kW.
Praview Liebert NXL UPS Installation Manual: 250-400kVA, 60Hz
This installation manual provides comprehensive instructions for the setup and installation of the Liebert NXL UPS, covering single-module and multi-module units ranging from 250-400kVA at 60Hz. It details safety precautions, mechanical and electrical installation procedures, environmental considerations, and system composition.
Praview Nota Keluaran Perisian Tegar Kad Perpaduan Liebert IntelliSlot v7.8.0.0
Nota keluaran untuk perisian tegar Liebert IntelliSlot Unity Card versi 7.8.0.0, memperincikan keserasian, ciri baharu, kemas kini keselamatan dan isu yang diketahui.