1. Produk Lebihview
The Sodeca REB-120 is an advanced heat recovery unit designed for efficient ventilation and energy saving in various applications. It features EC technology for low electrical consumption and an integrated bypass system for optimal performance across different seasons. This unit is engineered to recover heat with high efficiency, contributing to a comfortable indoor environment while reducing energy costs.
Its robust construction includes a counterflow plate heat exchanger and low-consumption fans with integrated regulation. The design allows for easy side access for maintenance. The unit is compatible with 50/60 Hz operation and includes particle filters for air quality.

Rajah 1: Depan view of the Sodeca REB-120 Heat Recovery Unit, showing its compact design and duct connections.
2. Ciri-ciri Utama
- EC Technology: Equipped with low-consumption fans for reduced electrical usage.
- Integrated Bypass: Features a 100% automatic bypass system (except for REB-15 model) for efficient operation in varying conditions.
- High Heat Recovery Efficiency: Achieves heat recovery efficiency of up to 79%.
- Counterflow Plate Heat Exchanger: Ensures effective heat transfer.
- Penyelenggaraan mudah: Designed with lateral access for convenient servicing.
- Pembinaan Tahan Lama: Structure made of galvanized steel with anti-condensation foam coating and expanded polypropylene interior.
- Reka bentuk padat: Pro rendahfile suitable for false ceiling installation.
- Particle Filters: Includes particle filters for improved air quality.
3. Persediaan dan Pemasangan
Proper installation is crucial for the optimal performance and longevity of your Sodeca REB-120 unit. It is highly recommended that installation be performed by a qualified professional in accordance with local building codes and regulations.
3.1 Senarai Semak Pra-Pemasangan
- Ensure the installation location provides adequate space for the unit and future maintenance access.
- Verify that the electrical supply matches the unit's requirements (compatible with 50/60 Hz).
- Confirm that ductwork is properly sized and sealed to prevent air leakage.
- Prepare a stable and level mounting surface, capable of supporting the unit's weight (91 kg).
3.2 Pemasangan dan Sambungan
The REB-120 is designed for installation in false ceilings or technical rooms. Securely mount the unit using appropriate fasteners. Connect the supply and exhaust air ducts to the designated ports. Ensure all electrical connections are made safely and correctly by a certified electrician.
Refer to the detailed installation diagrams provided in the separate technical manual for specific wiring and ducting configurations.
4. Arahan Operasi
Once installed and powered, the Sodeca REB-120 operates largely automatically, thanks to its integrated regulation and automatic bypass system.
4.1 Permulaan Awal
- After installation, ensure all access panels are securely closed.
- Apply power to the unit. The unit will typically perform a self-check.
- Monitor the unit for any unusual noises or vibrations during the first few minutes of operation.
4.2 Operasi Biasa
The unit's EC fans will adjust their speed to maintain optimal airflow and pressure. The automatic bypass will engage or disengage based on outdoor and indoor temperature differences to maximize heat recovery or provide free cooling when appropriate.
For advanced control and monitoring, consult the specific control panel manual (if applicable) or integrate with a building management system as per professional advice.
5. Penyelenggaraan
Regular maintenance ensures the efficiency and longevity of your heat recovery unit. Always disconnect power to the unit before performing any maintenance procedures.
5.1 Penggantian/Pembersihan Penapis
The particle filters should be inspected and cleaned or replaced regularly, typically every 3-6 months depending on air quality and usage. Dirty filters can significantly reduce airflow and efficiency.
- Locate the filter access panel (lateral access).
- Carefully remove the old filters.
- Clean reusable filters according to manufacturer guidelines or replace with new ones.
- Reinsert filters and secure the access panel.
5.2 Pembersihan Penukar Haba
Periodically, the heat exchanger may require cleaning to remove accumulated dust and debris. This should be done by a qualified technician, typically annually, to maintain optimal heat transfer efficiency.
5.3 Pemeriksaan Am
Regularly check for any signs of wear, damage, or unusual operation. Ensure all duct connections remain sealed. If any issues are detected, contact a qualified service technician.
6. Penyelesaian masalah
This section provides basic troubleshooting steps for common issues. For complex problems, always contact a qualified service technician.
| Masalah | Kemungkinan Punca | Penyelesaian |
|---|---|---|
| Unit tidak bermula | Tiada bekalan kuasa; pemutus litar terpelantik; pendawaian longgar. | Check power connection; reset circuit breaker; inspect wiring (by professional). |
| Pengurangan aliran udara | Clogged filters; blocked ducts; fan malfunction. | Clean or replace filters; check ducts for obstructions; contact service. |
| Bunyi yang tidak biasa | Loose components; fan imbalance; motor issue. | Inspect for loose parts; contact service for fan/motor issues. |
| Poor heat recovery | Dirty heat exchanger; bypass stuck open; sensor malfunction. | Clean heat exchanger (professional); contact service. |
7. Spesifikasi Teknikal
| Spesifikasi | Nilai |
|---|---|
| Pengeluar | Sodeca |
| Nombor Model | 1105712 (REB-120) |
| Dimensi Produk (L x W x H) | 148.8 x 113.2 x 39.5 cm |
| Berat Produk | 91 kg |
| warna | Kelabu |
| Komponen yang Disertakan | Unit Pemulihan Haba |
| Maximum Airflow (approx.) | 1440 m³/j |
| Heat Recovery Efficiency (approx.) | 79% |
8. Waranti dan Sokongan
Warranty information for the Sodeca REB-120 Heat Recovery Unit is typically provided at the point of purchase or included with the product documentation. Please retain your proof of purchase for warranty claims.
For technical support, service, or to inquire about replacement parts, please contact Sodeca customer service or an authorized Sodeca distributor in your region. Contact details can usually be found on the manufacturer's official webtapak atau pada pembungkusan produk.
Always ensure that any service or repairs are carried out by qualified and authorized personnel to maintain warranty validity and ensure safe operation.