SmartGen HAT560NB

SmartGen HAT560NB ATS Controller User Manual

1. Pengenalan

The SmartGen HAT560NB ATS Controller is an intelligent dual-supply module designed for Automatic Transfer Systems (ATS). It integrates digital, intelligent, and networked functionalities to provide precise voltage measurement and control for various power supply configurations. This controller is suitable for specialized ATS, Contactor ATS, and Air Break ATS applications, offering a compact structure, advanced circuitry, and high reliability.

It is engineered to reduce operational errors through automatic measurement and control, making it an ideal solution for managing power transfer between different sources like mains and generators.

SmartGen HAT560NB ATS Controller front view dengan paparan LCD dan butang kawalan

Rajah 1: Depan view of the SmartGen HAT560NB ATS Controller, showing the LCD display and operational buttons.

2. Features and Characteristics

The HAT560NB controller incorporates a powerful microprocessor for accurate monitoring and control. Key features include:

  • System type configuration: Mains (1#) & Generator (2#), Generator (1#) & Mains (2#), Mains (1#) & Mains (2#), Generator (1#) & Generator (2#).
  • 132x64 LCD with backlight, offering optional Chinese and English display with push-button operation.
  • Measurement and display of 2-way 3-phase voltage dan kekerapan.
  • Perlindungan terhadap over/under voltage, loss of phase, reverse phase sequence, and over/under frequency.
  • Automatic and Manual operating modes. Manual mode allows forced switch closure or opening.
  • All parameters are configurable on-site, secured by two different passwords for authorized access.
  • Genset commissioning can be set to On-load or Off-load mode.
  • Automatic re-closing function for the ATS Controller.
  • Configurable closing output signal as either on intervals or continuous output.
  • Applicable for ATS with one neutral position, two neutral positions, and non-position types.
  • Monitors 1-3 phase AC mains voltages.
  • Manages changeover of both generator and mains contactors.
  • Sends remote start commands to the generating set.
  • Compatible with various contactors and changeover switch types.

3. Persediaan dan Pemasangan

Proper installation is crucial for the safe and reliable operation of the HAT560NB controller. Ensure all power is disconnected before beginning installation. Refer to the wiring diagrams and terminal descriptions for correct connections.

3.1 Gambarajah Pendawaian

The HAT560NB controller supports various wiring configurations depending on the ATS type. Below are typical wiring diagrams for different setups. Always consult a qualified electrician for installation.

Multiple wiring diagrams for ATS controllers including ATYS3S, SGQ-N/T, SGQ-M, and VITZRO/PHETENG types

Figure 2: Comprehensive wiring diagrams illustrating connections for ATYS3S, SGQ-N/T, SGQ-M, and VITZRO/PHETENG ATS controller types. These diagrams show connections for 1# and 2# power supplies, load, and remote start signals.

Detailed wiring diagrams for SGQ-N/T, SGQ-M, and Contactor ATS configurations

Figure 3: Additional wiring diagrams focusing on SGQ-N/T, SGQ-M, and Contactor ATS configurations, detailing input and output connections for the controller.

3.2 Terminal Penyambung

The controller features clearly labeled terminals for power input, auxiliary outputs, and control signals. Ensure each wire is securely connected to its designated terminal.

belakang view of the HAT560NB controller showing labeled connecting terminals for inputs and outputs

Rajah 4: Belakang view of the HAT560NB controller, displaying the layout and labeling of all connecting terminals, including power inputs, auxiliary outputs, and communication ports.

4. Arahan Operasi

The HAT560NB controller offers both automatic and manual operation modes, accessible via its front panel buttons and LCD display.

4.1 Power On and Initial Display

Upon powering on, the LCD will display system information, including voltage and frequency readings for both power sources. The backlight ensures visibility in various lighting conditions.

4.2 Pemilihan Mod

  • Mod Automatik: The controller automatically monitors the power sources and initiates transfer based on pre-set parameters and detected abnormalities (e.g., over/under voltage, frequency deviations, phase loss).
  • Mod Manual: Allows the user to manually control the opening or closing of the transfer switches. This mode is typically used for testing or specific operational requirements.

4.3 Penetapan Parameter

All operational parameters can be configured directly on the unit using the push-buttons and LCD interface. Access to parameter settings is protected by a two-level password system to prevent unauthorized changes. Refer to the detailed programming guide (not included in this manual) for specific parameter definitions and adjustment procedures.

5. Penyelenggaraan

Regular maintenance ensures the longevity and reliable performance of your HAT560NB ATS Controller.

  • Pembersihan: Keep the controller's exterior clean and free from dust and debris. Use a soft, dry cloth. Avoid abrasive cleaners or solvents.
  • Pemeriksaan Sambungan: Periodically inspect all wiring connections to ensure they are secure and free from corrosion. Loose connections can lead to intermittent operation or system failures.
  • Keadaan Persekitaran: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent damage to internal components.

Untuk sebarang penyelenggaraan atau pembaikan dalaman, hubungi kakitangan servis yang berkelayakan.

6. Penyelesaian masalah

This section provides guidance on common issues you might encounter with the HAT560NB controller.

MasalahKemungkinan PuncaPenyelesaian
Pengawal tidak dihidupkanNo DC power supply; Incorrect wiringCheck DC 8.0V-35.0V power supply connections; Verify wiring according to diagrams.
ATS not transferring automaticallyAutomatic mode not selected; Fault detected on active power source (e.g., over/under voltage, frequency); Incorrect parametersEnsure controller is in Automatic mode; Check power source status; Verify parameter settings.
Display shows error for voltage / kekerapanActual power source issue; Sensor/input wiring problemSemak vol sebenartage and frequency of the power source; Inspect AC voltage pendawaian input.
Butang tidak bertindak balasTemporary software glitch; Hardware issueRestart the controller by cycling power; If issue persists, contact support.

7. Spesifikasi

The following table details the technical specifications for the SmartGen HAT560NB ATS Controller.

Table of specifications for SmartGen HAT560N series ATS Controller

Figure 5: Detailed specifications table for the HAT560N series ATS Controller, including operating voltage, power consumption, AC voltage input ranges, rated frequency, relay outputs, communication, dimensions, and environmental conditions.

itemSpesifikasi
Vol OperasitageDC 8.0V-35.0V (continuous power supply)
Vol. ACtage InputAC170V-270V (during AC power L1N1/L2N2 supply)
Penggunaan Kuasa<3W (mod siap sedia: <2W)
Kekerapan Dinilai50/60Hz
Tutup Output Geganti16A AC250V (Volts free output)
Output Geganti Bantu 17A AC250V (Volts free output)
Output Geganti Bantu 27A AC250V (Volts free output)
Output Geganti Bantu 316A AC250V (Volts free output)
Output Geganti Bantu 416A AC250V (Volts free output)
Input DigitalGND connect is active
KomunikasiAntara muka LINK, Protokol MODBUS
Dimensi Kes139mm x 120mm x 48mm (5.47 x 4.72 x 1.89 inci)
Potongan Panel130mm x 111mm
Keadaan KerjaTemperature: (-25~+70)°C, Humidity: (20~93)%RH
Keadaan PenyimpananSuhu: (-25~+70)°C
Tahap PerlindunganGasket IP55
Kekuatan PenebatGuna AC2.2kV voltage antara vol tinggitagterminal e dan vol rendahtage terminal; Arus kebocoran tidak lebih daripada 3mA dalam masa 1 minit.
Berat badan0.62kg (1.63 paun)

Dokumen Berkaitan - HAT560NB

Praview Manual Pengguna Pengawal HAT72 ATS
Manual pengguna untuk Pengawal Suis Pemindahan Automatik (ATS) Smartgen HAT72, memperincikan ciri-cirinya, parameter teknikal, operasi, sambungan terminal dan pendawaian biasa untuk pensuisan kuasa sesalur dan penjana. Direka untuk pemindahan kuasa automatik yang boleh dipercayai.
Praview Manual Pengguna Pengawal SmartGen HAT520N ATS
Manual pengguna untuk Pengawal ATS Dual Power SmartGen HAT520N, memperincikan prestasi, spesifikasi, operasi panel, konfigurasi parameter, pemasangan dan penyelesaian masalahnya.
Praview Manual Pengguna Pengawal SmartGen HAT530N ATS
This user manual provides comprehensive instructions and specifications for the SmartGen HAT530N ATS Controller. Learn about its features, operation, parameter settings, wiring diagrams, and troubleshooting.
Praview Manual Pengguna Pengawal ATS Pintasan Kuasa Berkembar Siri SmartGen HAT880
This user manual provides detailed operational and technical guidance for the SmartGen HAT880 Series Dual Power Bypass ATS Controller (HAT880/HAT880S), covering its features, specifications, operation, installation, and troubleshooting for reliable dual power management.
Praview Manual Pengguna dan Spesifikasi Suis Pemindahan Automatik (ATS) SmartGen HAT520N
Manual pengguna yang komprehensif dan spesifikasi teknikal untuk pengawal Suis Pemindahan Automatik (ATS) SmartGen HAT520N, meliputi operasi, keselamatan, pemasangan dan penyelesaian masalah untuk pelbagai konfigurasi bekalan kuasa.
Praview Manual Pengguna Pengawal SmartGen HAT520NC ATS
User manual for the SmartGen HAT520NC Automatic Transfer Switch (ATS) Controller, detailing its features, specifications, panel operations, wiring, installation, and troubleshooting.