Watt 0887709

Watts 0887709 Manual Arahan Kit Float & Vent 1/2" & 3/4"

For Watts 800M4-1/2 and 800M4-3/4 Vacuum Breakers

1. Pengenalan

This manual provides detailed instructions for the installation, function, maintenance, and troubleshooting of the Watts 0887709 Float & Vent Kit. This kit is specifically designed to repair the float and vent assembly in Watts 800M4-1/2 and 800M4-3/4 series vacuum breakers, restoring their proper operation and preventing backflow in plumbing systems.

2. Maklumat Keselamatan

3. Komponen Termasuk

The Watts 0887709 Float & Vent Kit includes the following essential components for repairing your vacuum breaker:

Watts 0887709 Float & Vent Kit components: vent disc holder assembly, vent spring, and bonnet O-ring

Imej 1: The Watts 0887709 Float & Vent Kit, showing the vent disc holder assembly (white plastic with red O-ring), a coiled metal spring, and a black rubber O-ring.

4. Pemasangan (Persediaan)

Follow these steps to replace the float and vent components in your Watts 800M4 vacuum breaker:

  1. Matikan Bekalan Air: Locate the main water shut-off valve for the irrigation system or the specific line connected to the vacuum breaker and turn it off completely.
  2. Melegakan Tekanan: Open any downstream valves or faucets to relieve pressure in the system.
  3. Disassemble the Bonnet: Carefully unscrew the bonnet of the Watts 800M4 vacuum breaker. This may require a wrench.
  4. Keluarkan Komponen Lama: Once the bonnet is removed, extract the old vent disc holder assembly, vent spring, and bonnet O-ring. Note their orientation for correct reassembly.
  5. Bersihkan Perumahan: Clean any debris or mineral deposits from the interior of the vacuum breaker housing and the bonnet.
  6. Pasang Komponen Baharu:
    • Place the new bonnet O-ring into its groove within the bonnet.
    • Insert the new vent spring into its designated position.
    • Carefully place the new vent disc holder assembly into the vacuum breaker body, ensuring it seats correctly.
  7. Reassemble the Bonnet: Screw the bonnet back onto the vacuum breaker body. Hand-tighten first, then use a wrench to snug it securely, but do not overtighten.
  8. Pulihkan Bekalan Air: Hidupkan semula bekalan air utama secara perlahan.
  9. Semak Kebocoran: Inspect the vacuum breaker for any signs of leaks. If leaks are present, turn off the water, re-check component seating, and tighten connections as necessary.
Close-up of the Watts vent disc holder assembly

Imej 2: Satu jarak dekat view of the vent disc holder assembly, a key component of the repair kit, showing its white plastic body and red sealing O-ring.

5. Function (Operating Principle)

The float and vent assembly within the Watts 800M4 vacuum breaker plays a critical role in preventing backflow. When the water supply pressure drops or a vacuum condition occurs, the float drops, opening the vent. This allows air to enter the system, breaking the vacuum and preventing contaminated water from being siphoned back into the potable water supply. When pressure is restored, the float rises, sealing the vent and allowing normal water flow.

6. Penyelenggaraan

Regular inspection and maintenance can extend the life of your vacuum breaker and ensure its continued effectiveness:

7. Penyelesaian masalah

Here are common issues and their potential solutions:

MasalahKemungkinan PuncaPenyelesaian
Constant LeakageWorn or improperly seated O-ring; damaged vent disc holder assembly.Turn off water, disassemble, inspect and replace O-rings and vent disc holder assembly. Ensure proper seating.
High-Pitched Whining NoiseWorn or deformed O-ring, causing vibration.Turn off water, disassemble, inspect and replace the bonnet O-ring and other seals.
Failure to Prevent BackflowDamaged or stuck float/vent assembly.Turn off water, disassemble, inspect the vent disc holder assembly and spring for damage or obstruction. Replace if necessary.
Aliran Air BerkurangDebris obstructing the vent or internal components.Turn off water, disassemble, and clean all internal components.

8. Spesifikasi

9. Maklumat Waranti

For specific warranty details regarding the Watts 0887709 Float & Vent Kit, please refer to the official Watts manufacturer's warranty policy. Warranty terms typically cover defects in materials and workmanship under normal use and service. Proof of purchase may be required for warranty claims.

10. Sokongan Pelanggan

If you require further assistance, have questions about installation, or need to report a product issue, please contact Watts customer support directly. You can typically find contact information, including phone numbers and online support portals, on the official Watts webtapak (www.watts.com).

Dokumen Berkaitan - 0887709

Praview Perhimpunan Pemutus Vakum Tekanan Siri Watts 800M4, LF800M4: Manual Pemasangan, Penyelenggaraan dan Pembaikan
Panduan komprehensif untuk memasang, menyelenggara dan membaiki Perhimpunan Pemutus Vakum Tekanan Siri Watts 800M4 dan LF800M4. Meliputi keselamatan, prosedur pemasangan, servis, perlindungan pembekuan dan jaminan.
Praview Senarai Harga Kelengkapan Paip Tekan-ke-Sambung Watts AquaLock™ 2025
Terokai senarai harga 2025 untuk kelengkapan paip push-to-connect Watts AquaLock™. Katalog komprehensif ini memperincikan kelengkapan loyang, plastik dan mini, termasuk spesifikasi teknikal, ciri dan panduan pemasangan untuk penyelesaian paip yang boleh dipercayai.
Praview Installation, Operation, and Maintenance Manual for Watts LFM115-74/LFM6115-74 Pressure Reducing Control Valves
Comprehensive guide for the installation, operation, maintenance, and troubleshooting of Watts LFM115-74 and LFM6115-74 Pressure Reducing Control Valves with Low Flow By-Pass. Includes detailed instructions, diagrams, and maintenance schedules.
Praview Watts N55B-M1 and LFN55B-M1 Water Pressure Reducing Valve Installation and Maintenance
Detailed installation, maintenance, and troubleshooting guide for Watts N55B-M1 and LFN55B-M1 Water Pressure Reducing Valves, including diagrams and warranty information.
Praview Watts H-PQ21X-16P Injap Bolong Udara Keluli Tahan Karat | Spesifikasi Teknikal & Panduan Pemasangan
Explore the Watts H-PQ21X-16P Series stainless steel air vent valve. This technical data sheet provides key features, operating principles, technical specifications, product codes, and installation guidance for plumbing and HVAC applications.
Praview Siri Teknik Spesifikasi Watt SL100XL, L100XL, LL100XL, LLL100XL
Teknik-teknik spesifikasi lengkap tuangkan les soupapes de décharge température and pression à tige allongée Watts series SL100XL, L100XL, LL100XL dan LLL100XL. Butiran sur les ciri-ciri, dimensi, pemasangan et sécurité pour chauffe-eau.