1. Pengenalan

This manual provides detailed instructions for the installation, operation, and maintenance of the Intermatic MIL72ESTUZH-120 24-Hour 120V Flush Mount Electromechanical Time Control. Please read this manual thoroughly before attempting to install or operate the device to ensure safe and correct usage.

2. Maklumat Keselamatan

WARNING: Risk of Electric Shock. Disconnect power at the circuit breaker or fuse box before installation or servicing.

  • Semua pendawaian mesti mematuhi kod elektrik tempatan dan nasional.
  • Pemasangan hendaklah dilakukan oleh juruelektrik yang bertauliah.
  • Jangan melebihi penarafan elektrik maksimum peranti.
  • Pastikan pembumian yang betul untuk mengelakkan bahaya elektrik.
  • Jauhkan kanak-kanak daripada peranti elektrik.

3. Produk Lebihview

The Intermatic MIL72ESTUZH-120 is a robust 24-hour electromechanical timer module designed for flush or panel mounting within a control panel. It is suitable for light-duty commercial applications requiring precise time control for 120 VAC single-phase circuits. Common uses include lighting, HVACR systems, pumps, motors, and general electrical circuit management.

Intermatic MIL72ESTUZH-120 24-Hour Electromechanical Time Control with a clear cover, showing the black dial with white markings for hours and minutes, and a manual override switch.

Imej: Depan view of the Intermatic MIL72ESTUZH-120 timer. The device features a clear protective cover over a black dial. The dial displays a 24-hour format with AM/PM indicators and minute markings. A central clock mechanism with hour and minute hands indicates the current time. The outer edge of the dial contains captive trippers for setting ON/OFF periods. A manual override switch is visible on the right side of the dial.

Ciri-ciri Utama:

  • 21 A SPDT Switch: Provides reliable switching for various loads.
  • Synchronous Drive with Self-Recharging Battery Backup: Ensures accurate timekeeping and operation during power outages.
  • Captive Trippers: Allows for easy setting of 15-minute ON/OFF intervals.
  • Pembatalan Manual: Provides flexibility to temporarily bypass programmed settings.
  • Reka bentuk Flush Mount: Integrates seamlessly into control panels.

4. Spesifikasi

SpesifikasiPerincian
Nombor ModelMIL72ESTUZH-120
JenamaIntermatik
Voltage120V
Jenis SuisSPDT (Balingan Berganda Kutub Tunggal)
Amppemadam21 A
Kitaran24-Jam
Jenis PemasanganFlush/Panel Mount
Sandaran BateriSelf-recharging Nickel Metal Hydride (non-replaceable)
Minimum ON/OFF Time15 minutes (using captive trippers)
bahanlogam
Dimensi Produk30"D x 8"W x 6"H (Note: These dimensions appear to be for packaging or a larger assembly, actual timer module dimensions will be smaller for flush mounting.)
Berat Barang4 auns

5. Pemasangan

Sebelum Anda Bermula:

  • Pastikan kuasa pada pemutus litar utama MATI.
  • Sahkan bahawa bekalan voltage matches the timer's rating (120V AC).
  • Have appropriate tools ready (screwdriver, wire strippers, etc.).

Pemasangan:

  1. Select a suitable location within a control panel for flush mounting.
  2. Cut an appropriate opening in the panel according to the timer's dimensions.
  3. Insert the timer into the opening and secure it using the provided mounting hardware.

Pendawaian:

Refer to the wiring diagram provided with the product packaging for specific connections. General wiring steps include:

  1. Connect the incoming 120V AC line wire to the designated terminal.
  2. Sambungkan wayar neutral ke terminal neutral.
  3. Connect the load wire(s) (e.g., to lights, motor) to the appropriate switched terminals (normally open or normally closed, depending on desired operation).
  4. Pastikan semua sambungan selamat dan terlindung.

After wiring, restore power and proceed to initial setup.

6. Operasi

Menetapkan Masa Semasa:

  1. Rotate the entire dial clockwise until the current time aligns with the time indicator arrow (usually a small triangle or line on the stationary part of the timer housing).
  2. Ensure you distinguish between AM and PM hours on the 24-hour dial.

Setting ON/OFF Programs:

The timer uses captive trippers around the dial to set program times. Each tripper represents a 15-minute interval.

  1. To set an ON period, push the trippers outwards for the desired duration.
  2. To set an OFF period, leave the trippers in their inward position for the desired duration.
  3. The timer will activate the connected load when the dial rotates past an outward-pushed tripper and deactivate it when it rotates past an inward-pushed tripper.

Pembatalan Manual:

The MIL72ESTUZH-120 features a manual override switch, typically a small lever or button, located on the timer face. This allows you to temporarily switch the load ON or OFF, overriding the programmed schedule without affecting future cycles.

  • Move the override switch to the desired position (ON or OFF).
  • The timer will resume its programmed schedule at the next scheduled ON or OFF event.

7. Penyelenggaraan

The Intermatic MIL72ESTUZH-120 is designed for minimal maintenance.

  • Pembersihan: Lap bahagian luar pemasa secara berkala dengan kain lembut dan kering. Jangan gunakan pembersih atau pelarut yang kasar.
  • Bateri: The unit contains a non-replaceable, self-recharging Nickel Metal Hydride battery for power outage carry-over. No user maintenance is required for the battery.
  • Pemeriksaan: Annually inspect the timer for any signs of damage, loose connections, or unusual operation. If any issues are found, disconnect power and consult a qualified electrician.

8. Penyelesaian masalah

MasalahKemungkinan PuncaPenyelesaian
Pemasa tidak berjalanNo power to the timer; Motor failureCheck circuit breaker/fuse; Verify wiring connections; Contact support if motor is faulty.
Load not turning ON/OFF at programmed timesIncorrect time setting; Trippers not set correctly; Manual override engagedAdjust current time; Ensure trippers are pushed in/out as desired; Check manual override switch position.
Manual override not workingSwitch mechanism faulty; Internal wiring issueEnsure switch is fully engaged; Contact support if issue persists.
Timer making unusual noisesIsu mekanikal dalamanDisconnect power immediately; Contact support.

9. Waranti dan Sokongan

For warranty information and technical support, please refer to the documentation included with your product or visit the official Intermatic webtapak. Simpan resit pembelian anda sebagai bukti pembelian untuk sebarang tuntutan waranti.

Intermatic Customer Support:

  • Webtapak: www.intermatic.com
  • Contact information can typically be found in the 'Support' or 'Contact Us' section of their webtapak.

Dokumen Berkaitan - MIL72ESTUZH-120

Praview Intermatic GM40AV Series Electromechanical Commercial Time Switch: Installation and Operation Manual
Comprehensive installation, operation, and programming guide for the Intermatic GM40AV Series electromechanical commercial time switches. Includes electrical ratings, wiring diagrams, and warranty information.
Praview Suis Masa Elektromekanikal Siri Intermatic T170, T1400 & T1800
Butiran komprehensif tentang Suis Masa Elektromekanikal 24 Jam Siri Intermatic T170, T1400 dan T1800, meliputi ciri, spesifikasi, penarafan, variasi model dan gambar rajah pendawaian untuk aplikasi komersial, perindustrian dan kediaman.
Praview Intermatic WHQ Series 40A Water Heater Timers with Battery Backup - Installation and Operation Manual
Detailed information on the Intermatic WHQ Series 24-Hour/7-Day electromechanical water heater timers, including features, specifications, installation guide, programming instructions, and warranty information. Designed for residential, commercial, and industrial use.
Praview Suis Masa Dail 24 Jam Intermatic T105: Panduan Pemasangan, Pendawaian dan Operasi
Panduan komprehensif untuk suis masa dail mekanikal 24 jam Intermatic T105. Meliputi spesifikasi model, amaran keselamatan, arahan pendawaian untuk pelbagai konfigurasi (SPNO, SPNC, SPDT), prosedur pengaturcaraan dan operasi manual. Termasuk jadual terperinci penarafan elektrik dan cadangan tolok wayar.
Praview Intermatic T103 24-Hour Dial Time Switch: Installation and Operation Manual
Detailed guide for the Intermatic T103 24-Hour Dial Time Switch, covering specifications, safety warnings, wiring instructions, programming, and operation. Suitable for indoor use with 120/208/240 VAC power.
Praview Intermatic T101P201/T101R201 24-Hour Time Switch with Fireman Switch
Detailed guide for Intermatic T101P201 (plastic) and T101R201 (metal) 24-hour dial time switches with fireman switch functionality for pool heaters. Includes wiring, programming, and operating instructions.