Watt 0063010

Watts 009M2 Reduced Pressure Zone Backflow Preventer (Model 0063010) Instruction Manual

For Models: 009M2, 009M2-QT

1. Pengenalan

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. Maklumat Keselamatan Penting

3. Produk Lebihview dan Komponen

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. Persediaan dan Pemasangan

  1. Semakan Prapemasangan:
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • Periksa unit tersebut untuk sebarang kerosakan penghantaran.
    • Ensure all necessary tools and materials for installation are available.
  2. Penyediaan Tapak:
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. Sambungan Paip:
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. Semakan Selepas Pemasangan:
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • Periksa semua sambungan untuk kebocoran.
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. Arahan Operasi

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

6. Penyelenggaraan

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

7. Penyelesaian masalah

MasalahKemungkinan PuncaPenyelesaian
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
Tiada aliran air atau aliran berkurangan
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Ensure shutoff valves are fully open.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
Kebocoran daripada sambungan
  • Benang yang tidak dimeterai dengan betul
  • Damaged gaskets
  • Re-apply thread sealant and tighten connections.
  • Inspect and replace gaskets.

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. Spesifikasi

Nombor Model0063010 (009M2)
Backflow Preventer TypePerhimpunan Zon Tekanan Dikurangkan
Bahan BadanGangsa
Inlet/Outlet Connection Size2 Inches (50 MM)
Inlet/Outlet Connection TypeFemale Threaded NPT
Tekanan Kerja Maksimum175 PSI (12.10 BAR)
Suhu Maksimum180°F (82°C)
Suhu minimum33°F (0.5°C)
Jenis PerlindunganBackpressure and Backsiphonage
Dimensi Produk (L x W x H)22 x 10 x 8 inci
Berat Barang27 paun
Lead Free StatusNO (For non-potable use only)

9. Waranti dan Sokongan

Specific warranty information for Watts products is typically provided with the product packaging or available on the official Watts weblaman web. Sila rujuk sumber ini untuk terma dan syarat jaminan terkini.

For technical support, replacement parts, or further assistance, please contact Watts customer service or visit their official website. Ensure you have your product model number (0063010) and serial number (if applicable) ready when contacting support.

Watts Official Webtapak: www.watts.com

Dokumen Berkaitan - 0063010

Praview Watts LF909 Series Reduced Pressure Zone Assembly Engineering Specification
Comprehensive engineering specification for the Watts LF909 Series Reduced Pressure Zone Assembly (21⁄2" - 10"). Details features, operation, materials, dimensions, and capacity for this Lead Free backflow prevention device with integrated flood sensor.
Praview Watts Series 009, LF009, LFU009, SS009, U009: Installation, Maintenance, and Repair Manual
This comprehensive manual from Watts provides essential guidance for the installation, maintenance, and repair of the Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies. It details safety warnings, installation procedures, inspection, servicing, troubleshooting, and warranty information for these critical backflow prevention devices.
Praview Watts Series 909, LF909, 909RPDA Reduced Pressure Zone Assemblies Installation, Maintenance, and Repair Manual
Comprehensive guide for the installation, maintenance, and repair of Watts Series 909, LF909, and 909RPDA Reduced Pressure Zone Assemblies, including safety warnings, installation guidelines, testing procedures, servicing instructions, troubleshooting, and warranty information.
Praview Watts Series LF909 Reduced Pressure Zone Assemblies - Technical Specification
Detailed technical specifications for Watts Series LF909 Reduced Pressure Zone Assemblies, including features, operation, dimensions, weights, and capacity. Designed for potable water cross-connection control.
Praview Watts Series 009, LF009, LFU009, SS009, U009 Reduced Pressure Zone Assemblies Installation, Maintenance, and Repair Manual
Comprehensive guide for the installation, maintenance, and repair of Watts Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies, covering safety, installation procedures, annual inspection, troubleshooting, and service. Includes details on flood sensor activation and connection kits.
Praview Watts Series LF919 Reduced Pressure Zone Assembly: Installation, Maintenance, and Repair Manual
Comprehensive guide for installing, maintaining, and repairing the Watts Series LF919 Reduced Pressure Zone Assembly (1/2" - 2"). Includes safety warnings, installation procedures, servicing instructions, and troubleshooting.