Philips Lighting ER55LD3WR

Manual Pengguna Papan Tanda Keluar LED Philips Lighting ER55LD3WR

Model: ER55LD3WR

pengenalan

This manual provides essential information for the safe and efficient use of your Philips Lighting ER55LD3WR LED Exit Sign. Please read these instructions carefully before installation and operation, and retain them for future reference. This product is designed for commercial lighting applications, specifically as a lighted exit sign.

Maklumat Keselamatan

  • Always disconnect power before installing or servicing the unit.
  • Pemasangan hendaklah dilakukan oleh juruelektrik yang berkelayakan mengikut kod elektrik kebangsaan dan tempatan.
  • Jangan gunakan produk ini untuk tujuan selain daripada penggunaan yang dimaksudkan.
  • Pastikan semua sambungan selamat dan terlindung dengan betul.
  • Jauhkan daripada air dan kelembapan berlebihan.

Kandungan Pakej

Sahkan bahawa semua komponen hadir sebelum memulakan pemasangan:

  • Philips Lighting ER55LD3WR LED Exit Sign unit
  • Perkakasan pemasangan (skru, sauh)
  • Manual Arahan (dokumen ini)

Persediaan dan Pemasangan

The Philips Lighting ER55LD3WR LED Exit Sign is designed for wall mounting. Ensure the mounting surface is suitable to support the weight of the unit.

  1. Sediakan Kawasan Pemasangan: Disconnect power to the circuit where the exit sign will be installed.
  2. Pemasangan:
    • Identify the desired wall mounting location.
    • Use the provided mounting hardware to securely attach the exit sign to the wall. Ensure the unit is level.
  3. Pendawaian:
    • Connect the building's 120V AC power supply to the corresponding wires on the exit sign. Refer to the wiring diagram inside the unit's housing for specific connections.
    • Pastikan pembumian yang betul.
    • Connect the internal battery (if not pre-connected). This is crucial for emergency operation.
  4. Perhimpunan Akhir: Secure any covers or diffusers.
Philips Lighting ER55LD3WR LED Exit Sign, front view

Rajah 1: Depan view of the Philips Lighting ER55LD3WR LED Exit Sign. This image shows the white housing with the red "EXIT" lettering illuminated, indicating its primary function as an emergency egress indicator.

Arahan Operasi

Once installed and power is restored, the Philips Lighting ER55LD3WR LED Exit Sign will operate automatically.

  • Operasi Biasa: When AC power is present, the "EXIT" sign will be illuminated by the internal LEDs. The green indicator light on the unit will be ON, signifying operating status.
  • Operasi Kecemasan: In the event of an AC power failure, the unit will automatically switch to battery backup, illuminating the "EXIT" sign for a specified duration (typically 90 minutes).
  • Butang Ujian: A test button is provided on the unit to verify emergency operation. Press and hold the "Push to Test" button to simulate an AC power failure. The sign should remain illuminated, and the green indicator light will blink, indicating testing. Release the button to return to normal operation.
Philips Lighting ER55LD3WR LED Exit Sign, test button and indicator lights

Rajah 2: Jarak dekat view of the test button and indicator lights on the Philips Lighting ER55LD3WR LED Exit Sign. The green indicator shows operating status (ON for ready, Blinking for testing). The red indicator shows service alerts such as battery, charger board, transformer, or LED strip faults.

Penyelenggaraan

Regular maintenance ensures the reliability and longevity of your LED Exit Sign.

  • Ujian Bulanan: Press the "Push to Test" button for at least 30 seconds to ensure the battery backup system is functioning. The sign should remain illuminated.
  • Annual Test: Disconnect AC power to the unit for 90 minutes to verify the battery can sustain emergency illumination for the required duration.
  • Pembersihan: Bersihkan bahagian luar unit dengan lembut, damp kain. Jangan gunakan pembersih atau pelarut yang melelas.
  • Penggantian Bateri: The internal battery has a limited lifespan. If the unit fails to hold a charge or the red "Battery fault" indicator illuminates, the battery may need replacement. Contact qualified service personnel for battery replacement.

Menyelesaikan masalah

Rujuk jadual berikut untuk isu biasa dan penyelesaiannya.

MasalahKemungkinan PuncaPenyelesaian
Sign does not illuminate (AC power present)No AC power; faulty wiring; LED strip faultCheck circuit breaker; verify wiring connections; contact service for LED replacement.
Sign does not illuminate during power outage (mod kecemasan)Battery not connected; discharged battery; faulty battery; charger board faultEnsure battery is connected; allow 24 hours for initial charge; replace battery; contact service for charger board repair.
Red Service Alert indicator is ONIndicates battery, charger board, transformer, or LED strip fault (refer to unit label)Identify specific fault from unit label; perform monthly/annual tests; contact qualified service personnel.
Green Operating Status indicator is OFF (AC power present)No AC power; internal faultCheck AC power supply; contact qualified service personnel.

Spesifikasi

CiriPerincian
Nombor ModelER55LD3WR
JenamaPencahayaan Philips
Jenis Sumber CahayaLED
Voltage120 Volt
Sumber KuasaElektrik Bertali
Jenis PemasanganLekap di dinding
bahanlogam
warnaputih
Dimensi Produk4.25 x 6.25 x 4.8 inci
Berat Barang4.98 paun
UPC781370410117

Waranti dan Sokongan

For warranty information or technical support, please contact Philips Lighting customer service. Keep your purchase receipt as proof of purchase.

Pengeluar: Pencahayaan Philips

Webtapak: Lawati Kedai PHILIPS di Amazon

Dokumen Berkaitan - ER55LD3WR

Praview Helaian Data Lampu LED Kuasa Tinggi Philips RoadForce BRP481 LED60 NW 33W DWL P7 0-10
Lembaran data teknikal untuk Philips RoadForce BRP481 LED60 NW 33W DWL P7 0-10, sebuah luminair LED berkecekapan tinggi dengan ciri, spesifikasi dan data aplikasi termaju. Termasuk butiran prestasi, mekanikal dan elektrik.
Praview Philips TubePoint: Julat Luminair Berprestasi Tinggi untuk Terowong Lalu Lintas
Explore the Philips TubePoint luminaire range, engineered for efficient, cost-effective, and reliable lighting solutions in traffic tunnels. This product family leaflet details features, benefits, technical specifications, and model variations for optimal tunnel illumination.
Praview Manual Kualiti Pencahayaan Philips
This Quality Manual outlines the Philips Lighting Quality System, detailing its processes, standards, and commitment to quality. It serves as a supplement to the Philips Lighting Business System, ensuring products and services meet ISO 9001 requirements and customer expectations.
Praview Lampu LED Pelekap Dinding Philips CoreLine
Discover the Philips CoreLine Wall-Mounted LED luminaire, an innovative, easy-to-use, and high-quality lighting solution for various applications like corridors, staircases, and public entrances. This brochure details its features, benefits, technical specifications, and product information.
Praview Philips OccuSwitch LRM1070/00 PIR Anwesenheitssensor Datenblatt
Datenblatt für den intelligenten Philips OccuSwitch LRM1070/00 Anwesenheitssensor. Bietet PIR-Technologie, tageslichtabhängige Schaltung, integriertes Relais und Deckeneinbau. Enthält technische Spezifikationen und Abmessungen.
Praview Pengesan Gerakan dan Suis Lampu Philips OccuSwitch LRM1070/00
Discover the Philips OccuSwitch LRM1070/00, an intelligent motion detector with an integrated switch designed to save energy by automatically turning off lights in unoccupied rooms. Ideal for spaces up to 25 m², it handles loads up to 6A and features easy installation with a detachable connector.