General Electric SELA36AT0150

Manual Pengguna Pemutus Litar GE SELA36AT0150

Model: SELA36AT0150 | Brand: General Electric

1. Pengenalan dan Selesai Produkview

This manual provides essential information for the safe and effective use of the GE SELA36AT0150 Bolt-On Mount Type SEL Molded Case Circuit Breaker. This current-limiting circuit breaker is designed for industrial and commercial applications, providing protection against overcurrents and short circuits.

Ciri-ciri utama termasuk:

  • Current Limiting Circuit Breaker: Designed to limit the magnitude and duration of short-circuit currents.
  • 150 Amps Max | 150 A Rating Plug: Configured for a maximum current of 150 Amps with a corresponding rating plug.
  • 3 Pole, 480/600 VAC: Suitable for three-phase alternating current systems up to 600 Volts.
  • Spectra RMS Series: Part of the GE Spectra RMS line, known for advanced protection features.
  • Bolt-On Mount: Designed for secure bolt-on installation.
GE SELA36AT0150 Circuit Breaker Front View

Rajah 1: Depan view of the GE SELA36AT0150 Circuit Breaker, showing the ON/OFF switch and product labels.

2. Maklumat Keselamatan

AMARAN: Installation, maintenance, and troubleshooting of electrical equipment should only be performed by qualified and licensed electricians. Failure to follow these instructions can result in serious injury, death, or property damage.

  • Always disconnect power before working on electrical circuits or equipment.
  • Gunakan peralatan perlindungan diri (PPE) yang sesuai, termasuk sarung tangan terlindung dan pelindung mata.
  • Verify all connections are secure and properly torqued according to specifications.
  • Ensure the circuit breaker's ratings match the system requirements.

3. Persediaan dan Pemasangan

The GE SELA36AT0150 is a bolt-on mount circuit breaker. Proper installation is crucial for safe and reliable operation.

3.1 Pemeriksaan Pra-Pemasangan

  • Confirm the circuit breaker's voltage, current, and interrupting ratings are compatible with the electrical system.
  • Inspect the circuit breaker for any physical damage. Do not install damaged units.
  • Pastikan permukaan pelekap bersih, kering dan kukuh dari segi struktur.

3.2 Arahan Pemasangan

  1. De-energize the electrical panel or system where the breaker will be installed. Verify zero voltage dengan multimeter.
  2. Position the circuit breaker in the designated slot or mounting location.
  3. Secure the breaker using appropriate bolts and hardware for bolt-on mounting. Ensure it is firmly seated.
  4. Connect the load and line conductors to the appropriate terminals. The breaker includes a set of bottom lugs.
  5. Refer to the product label for specific wire ranges and torque specifications:
    • Wire Range: #12 - 3/0 CU, #12 - 3/0 AL
    • Torque: #12-#10: 35 lb-in, #8-#3: 100 lb-in, #2-3/0: 150 lb-in
  6. Periksa semula semua sambungan untuk memastikan ketat dan penebat yang betul.
GE SELA36AT0150 Circuit Breaker Label with Specifications

Figure 2: Close-up of the circuit breaker's main label, detailing Cat No., Amp rating, Voltage, Pole configuration, Rating Plug Type, Lug Data, Wire Range, and Torque specifications.

GE SELA36AT0150 Circuit Breaker Interrupting Rating Label

Figure 3: Close-up of the circuit breaker's interrupting rating label, showing RMS Symmetrical Amps at various voltages (240V, 480V, 600V) and international standards.

GE SELA36AT0150 Circuit Breaker Rear View

Rajah 4: Belakang view of the GE SELA36AT0150 Circuit Breaker, showing the bolt-on mounting points and terminal connections.

4. Arahan Operasi

The GE SELA36AT0150 circuit breaker is designed for simple operation, primarily acting as an ON/OFF switch and an automatic protective device.

4.1 Menghidupkan/Mematikan

  • Untuk memutar litar ON, firmly push the handle to the "ON" position.
  • Untuk memutar litar DIMATIKAN, firmly push the handle to the "OFF" position.

4.2 Tripping and Resetting

If an overcurrent or short circuit condition occurs, the breaker will automatically "trip" to the center position (between ON and OFF) to protect the circuit. To reset a tripped breaker:

  1. First, move the handle completely to the "OFF" position. This resets the internal mechanism.
  2. Investigate and resolve the cause of the trip (e.g., overloaded circuit, short circuit).
  3. Once the issue is resolved, firmly push the handle to the "ON" position to restore power.
  4. If the breaker immediately trips again, do not attempt to reset it repeatedly. Consult a qualified electrician.

5. Penyelenggaraan

Pemutus litar biasanya memerlukan penyelenggaraan yang minimum. Walau bagaimanapun, pemeriksaan berkala disyorkan untuk memastikan operasi selamat berterusan.

  • Pemeriksaan Visual: Annually inspect the breaker for signs of physical damage, discoloration, or loose connections.
  • Pembersihan: Keep the area around the breaker clean and free of dust and debris. Use a dry, non-conductive cloth for cleaning. Do not use liquids.
  • Pemeriksaan Sambungan: Periodically (e.g., every 3-5 years, or as per local codes) have a qualified electrician check the tightness of terminal connections.
  • Ujian: For critical applications, periodic testing of the breaker's trip mechanism by a qualified professional may be required.

Nota: Do not attempt to open or repair the circuit breaker. There are no user-serviceable parts inside.

6. Penyelesaian masalah

Bahagian ini menangani isu biasa yang mungkin anda hadapi dengan pemutus litar anda.

MasalahKemungkinan PuncaPenyelesaian
Perjalanan pemutus kerap.Litar terlebih beban, litar pintas, kerosakan pembumian atau perkakas yang rosak.Kurangkan beban pada litar. Cabut plag peralatan. Periksa pendawaian untuk kerosakan. Jika masalah berterusan, rujuk juruelektrik yang berkelayakan.
Pemutus tidak akan ditetapkan semula.Persistent fault (short circuit/overload) or internal breaker damage.Ensure the handle is pushed fully to "OFF" before attempting to reset. If it still won't reset, do not force it. Call a qualified electrician.
Tiada kuasa ke litar, tetapi pemutus litar ON.Loose connection, wiring issue, or internal breaker failure.This indicates a serious issue. Immediately turn off the breaker and consult a qualified electrician. Do not attempt to diagnose or fix yourself.

For any issues not covered here, or if troubleshooting steps do not resolve the problem, always contact a qualified and licensed electrician.

7. Spesifikasi

Detailed technical specifications for the GE SELA36AT0150 Circuit Breaker:

AtributNilai
Nombor ModelSELA36AT0150
JenamaGeneral Electric
Penilaian Semasa150 Amps
Voltage Peringkat480 / 600 VAC
Bilangan Tiang3
Jenis Pemutus LitarStandard, Current Limiting, Molded Case
Jenis PemasanganBolt-On Mount
Interrupting Rating @ 240 VAC100,000 Amps
Interrupting Rating @ 480 VAC65,000 Amps
Interrupting Rating @ 600 VAC25,000 Amps
Rating Plug TypeSRPE150A
Rating Plug Inst. Adjustable Range450-1991 A (Lo to Hi)
Dimensi Produk (D x W x H)4" x 4" x 6.5" (anggaran)
Berat badan4.8 lbs (anggaran)
Tarikh Mula-mula Tersedia11 Oktober 2012

8. Waranti dan Sokongan

For specific warranty information regarding your GE SELA36AT0150 Circuit Breaker, please refer to the documentation provided at the time of purchase or contact General Electric directly. As a general guideline, electrical components typically come with a manufacturer's warranty covering defects in materials and workmanship.

For technical support, service, or to inquire about replacement parts, please contact General Electric customer service or visit their official webtapak. Anda juga boleh melawat GE Store on Amazon for more information on GE products.

Always ensure that any work on electrical systems is performed by qualified and licensed professionals.

9. Video Produk Rasmi

No official product videos from the seller were found for this specific model in the provided data. For general product information or installation guides, please check the manufacturer's official webtapak atau pengedar sah.

© 2024 General Electric. All rights reserved. This manual is for informational purposes only.

Ask a question about this manual